112.5 kVA 11 kV Oil Immersed Transformer: S11 Series Specifications
Nov 10, 2025
Leave a message
Overview of the 112.5 kVA 11 kV Oil Immersed Transformer
The 112.5 kVA oil immersed transformer is a three-phase distribution transformer with a rated primary voltage of 11 kV and a secondary voltage of 0.4 kV. It is a hermetically sealed unit with a corrugated tank, designed for the lower end of the distribution network where compact size, low loss and long service life are the priority. The model designation S11-112.5-11/0.4 kV refers to an S11 loss class, a 112.5 kVA rating and an 11 kV to 0.4 kV ratio.
The unit is built and tested to IEC 60076, with routine tests covering ratio, vector group, winding resistance, no-load loss and current, load loss and impedance, and dielectric withstand.
Technical Specifications
| Parameter | Value |
|---|---|
| Model | S11-112.5 kVA-11/0.4 kV |
| Type | Oil immersed power transformer |
| Standard | IEC 60076 |
| Rated power | 112.5 kVA |
| Frequency | 50 Hz |
| Phase | Three |
| Cooling type | ONAF |
| Primary voltage | 11 kV |
| Secondary voltage | 0.4 kV |
| Winding material | Copper |
| Vector group | Dyn11 |
| Impedance voltage | 4% |
| Tap changer | Off-circuit, +/-2 x 2.5% |
| No-load loss | 0.24 kW |
| Load loss at 75 C | 1.8 kW |
Corrugated Tank Design
The corrugated tank is a defining feature of this class of transformer. Instead of pressed steel radiators, the tank walls are formed into vertical corrugations that act as cooling fins. The finned surface provides more effective heat exchange per unit of floor area than conventional radiators, which makes the transformer compact and light while improving cooling. Because the tank is hermetically sealed, the insulating oil never contacts the atmosphere, so moisture and oxygen cannot enter and the oil keeps its dielectric strength for a long service life.
Corrugated tanks are available across the 11 kV and 33 kV classes up to about 2500 kVA. The design is space-saving, reliable and quiet, and it eliminates the oil leaks associated with bolted radiator joints.
Applications
Power distribution: stepping 11 kV down to 0.4 kV for final distribution to consumers.
Commercial and industrial facilities: powering equipment in smaller commercial buildings, factories and industrial sites fed by an 11 kV line.
Lighting systems: supplying commercial and residential lighting circuits.
Outdoor installation: the sealed outdoor construction suits pole, plinth and compound mounting in rural and urban networks.
Performance and Efficiency
With a no-load loss of 0.24 kW and a load loss of 1.8 kW at 75 C, the full-load efficiency of the unit is approximately 98.2%, calculated from the rated power and the sum of the two losses, and the efficiency peaks at partial load, which matches the typical loading profile of a rural distribution transformer. The low no-load loss is particularly valuable because the transformer is energized continuously, so the no-load component accrues around the clock, while load loss varies with the square of the load factor.
The performance parameters that define the unit are the impedance voltage, which sets the voltage regulation and short-circuit current; the no-load current, which reflects the quality of the core material and the joint construction; the no-load loss, driven by the silicon steel grade and stacking; and the short-circuit loss, driven by the winding material and design.
Selection and Operation Notes
Verify that the vector group and impedance match the existing network; a mismatch changes the fault levels and parallel operation behaviour.
Check the tapping range against the actual primary voltage at the site; off-circuit tap changers must be set before energization.
Take an oil sample for breakdown voltage and dissolved gas analysis at commissioning and then annually.
Keep the tank sealed during service; opening it without drying equipment introduces moisture that accelerates oil ageing.
For 60 Hz networks, the ratio and losses should be re-evaluated, since core loss rises with frequency.
FAQ
What does S11 mean in the model designation?
S11 is the loss class of the transformer under the Chinese standard system: S stands for three-phase oil-immersed and 11 indicates a specific level of no-load and load loss, lower than the older S9 class.
What is the difference between NLTC and OLTC?
NLTC, off-circuit tap changing, means the tapping position can only be changed when the transformer is de-energized. OLTC, on-load tap changing, allows voltage adjustment while the transformer is live, at higher cost and complexity. Distribution transformers normally use NLTC.
Why choose a corrugated tank instead of radiators?
The corrugated tank uses the tank wall itself as a cooling surface, which saves space and weight, improves cooling, and removes the bolted joints that can leak oil in radiator designs.
What efficiency can be expected from a 112.5 kVA transformer?
With a no-load loss of 0.24 kW and a load loss of 1.8 kW, full-load efficiency is approximately 98.2%, and efficiency is slightly higher at partial load, for example around 98.5% at 75% load.
Can this transformer be used at 60 Hz?
The unit is designed for 50 Hz. Operation at 60 Hz raises core loss and changes the flux density, so the design must be re-evaluated; a dedicated 60 Hz version with an adjusted core and ratio is normally required.
What accessories are included in the standard configuration?
The standard configuration includes the corrugated tank, bushings, oil drain and sampling valves, lifting lugs, rating plate, and the off-circuit tap changer, with optional additions such as a thermometer, oil level gauge, pressure relief device and gas relay.