SCB Series Dry-Type Transformer Features
Apr 11, 2024
Leave a message
What Is the SCB Series?
The SCB series is a family of three-phase cast-resin dry-type transformers in which the low-voltage and high-voltage windings are cast into epoxy resin under vacuum. The resin encapsulation seals the windings against moisture, dust and corrosive atmospheres, provides the main insulation, and gives the transformer a smooth surface that is easy to clean. The series is divided into performance classes SCB9, SCB10, SCB11 and SCB13, where the number indicates the loss level: the higher the number, the lower the no-load and load losses and the higher the efficiency.
Voltage and Capacity Range
SCB series transformers are manufactured for primary voltages of 6.6 kV, 10 kV, 11 kV, 13.8 kV, 15 kV, 22 kV, 33 kV and 35 kV, and for capacities from 30 kVA to 5000 kVA. The secondary voltage is normally 400 V or 415 V for distribution duty, with other combinations available for special applications. The wide range covers the typical medium-voltage distribution levels used in commercial and industrial installations around the world.
Main Features
Maintenance-free operation: the epoxy-encapsulated windings need no periodic oil testing or drying, which reduces the lifetime service cost
Low loss: the grain-oriented silicon steel core and the optimized winding design keep the no-load and load losses within the declared performance class
Low noise: the compact core construction and the rigid resin encapsulation limit the magnetostriction noise of the core
Low temperature rise: the cooling channels between the cast coils allow effective air circulation, keeping the winding temperature within the insulation class
High short-circuit resistance: the cast resin coils withstand the mechanical forces of short-circuit currents without deformation
Fire safety: the resin is flame retardant, self-extinguishing and does not drip burning material, so the unit is fireproof and explosion-proof
Environmental friendliness: no oil means no leakage risk and no pollution of the installation room
Moisture resistance: the encapsulation protects the windings against condensation and high humidity, and the unit can be re-energized after a shutdown without drying
Working Environment
| Parameter | Limit |
|---|---|
| Working temperature | -25 C to +40 C |
| Relative humidity | Below 70% average; monthly average 90% at 20 C |
| Altitude | Below 1000 m (derating applies above) |
| Installation | Indoor, ventilated, non-corrosive atmosphere |
For installations above 1000 m or with an ambient temperature outside this range, the rated capacity is derated according to the rules of the applicable standard, or the unit is specially designed for the site conditions.
Typical Applications
SCB series transformers are installed in urban power grids, high-rise buildings, business centers, theaters, hospitals, hotels, tunnels, subways, high-speed rail stations and airports. These locations share two requirements: a high level of fire safety, because the transformer room is close to occupied areas, and a low maintenance burden, because the access for service is limited. The dry-type, cast-resin construction satisfies both requirements, and the low noise level is an additional benefit in buildings where the transformer room is adjacent to offices or wards.
Standards and Testing
SCB series transformers are designed, tested and loaded in accordance with IEC 60076-11 for dry-type power transformers and with GB/T 10228 for dry-type power transformers in China. The routine tests include winding resistance, voltage ratio, insulation resistance, induced overvoltage, partial discharge and temperature rise, and the sound level is verified against the declared value. These tests are documented in the test report delivered with each unit.
Frequently Asked Questions
What does the number in SCB10 or SCB13 mean?
The number indicates the loss level of the transformer. A higher number corresponds to lower no-load and load losses, which means higher efficiency and lower lifetime energy cost, at a higher initial purchase price.
Can an SCB transformer be installed outdoors?
The standard SCB unit is designed for indoor installation. For outdoor duty, a weatherproof enclosure or a transformer room is required to protect the unit from rain, direct sunlight and pollution.
What is the difference between a cast-resin and a VPI dry-type transformer?
In a cast-resin transformer the windings are cast into solid epoxy blocks, which gives the best moisture and pollution protection. In a VPI unit the windings are vacuum-pressure impregnated with resin but the surface remains open, which allows higher overload capability at the cost of lower environmental protection.
How long can an SCB transformer be out of service?
Because the windings are encapsulated, the unit can be re-energized after a long shutdown without a drying procedure, as long as the insulation resistance measured before energizing meets the acceptance value of the standard.
Why is the SCB transformer preferred for high-rise buildings?
Buildings require fireproof, maintenance-free equipment that can be installed close to the load. The cast-resin construction is flame retardant and self-extinguishing, needs no oil containment, and produces no toxic gas in a fire.
How is the temperature of the windings monitored?
PT100 temperature sensors are embedded in the low-voltage windings and connected to a temperature controller that displays the winding temperature, activates the forced-air cooling fans when set points are reached, and trips the circuit breaker on overtemperature.