1600 kVA Oil Immersed Transformer: Impedance, Cooling Class and Load Capability
Nov 06, 2025
Leave a message
Where a 1600 kVA Oil-Immersed Transformer Fits
A 1600 kVA oil-immersed transformer is a medium-size distribution and substation unit. It is used for step-down duty between the local medium-voltage busbar and a 0.4 kV or 0.69 kV switchboard supplying a whole plant, and it is also used for step-up duty at generation and energy-storage sites. In a small or medium substation it is often the main transformer that feeds everything downstream, which means its availability directly determines the availability of the process it serves.
At this rating the design is no longer a commodity item. Impedance, cooling class, tap range and loss performance are all specified by the buyer, because the transformer's impedance determines the short-circuit current that the LV switchgear must interrupt, and its losses determine a substantial part of the site's energy cost over a twenty to thirty year life.
Core, Windings and Impedance
The core is a stacked, mitred-joint lamination assembly built from grain-oriented silicon steel. IEC 60404-8-7 defines the grade designation system for this material and guarantees the maximum specific total loss at 1.7 T and 50 Hz, so the grade chosen directly sets the no-load loss. Because the ratio of no-load to load loss determines which loss component dominates the annual energy bill, units that spend most of their time lightly loaded are normally specified with a high-permeability, low-loss grade.
Both windings are wound from copper. The HV winding is arranged in a multi-layer cylindrical or disc pattern with a tap section brought out to an off-circuit or on-load tap changer; the LV winding uses copper conductor sized for the full secondary current. The transformer uses a Dyn11 connection symbol, which blocks the transfer of triplen harmonics and limits the effect of unbalanced, uncompensated load on the supply quality. Short-circuit impedance for a unit in this size class is typically in the region of 5 to 6 %, but the exact value is fixed by the order specification because it sets the fault level seen by the LV switchboard.
| Parameter | Typical range |
|---|---|
| Rated capacity | 1600 kVA |
| HV winding | 10 kV, 11 kV, 20 kV or 33 kV |
| LV winding | 0.4 kV, 0.415 kV, 0.69 kV |
| Insulation level at Um 12 kV | 75 kV peak LI, 28 kV rms AC (IEC 60076-3) |
| Core lamination thickness | 0.18 mm to 0.30 mm grain-oriented grades |
| Cooling | ONAN or ONAN/ONAF |
| Temperature rise (IEC 60076-2) | 60 K top oil, 65 K average winding for ONAN |
Cooling, Tank and Internal Protection
At 1600 kVA the heat to be rejected is large enough that cooling class becomes a design decision. A plain ONAN tank with radiators may be sufficient for a lightly loaded unit in a temperate climate; where the site is hot or the load profile is severe, fans are added so that the same tank can carry more load in the ONAF stage. Oil is circulated by natural convection, drawn through vacuum oil-filling at the works so that bubbles trapped in the core and winding insulation are removed before sealing.
The tank is equipped with a pressure relief device and a gas relay. The relief valve vents an abnormal internal pressure produced by an arc or a severe fault and reseats when pressure falls back to normal; the gas relay gives an alarm on slow gas accumulation and trips on the sudden oil surge that characterises a major fault. A thermometer pocket accepts a dial gauge with alarm and trip contacts, and bushings are rated for the external creepage distance of the site's pollution class.
Testing and Load Capability
Tests are carried out in accordance with IEC 60076-1, with the individual chapters applying as follows: IEC 60076-2 for temperature rise, IEC 60076-3 for insulation levels and dielectric tests, IEC 60076-5 for the ability to withstand a symmetrical short circuit - the standard duration being 2 s - and IEC 60076-10 for the determination of sound power and sound pressure levels. Impulse testing of the HV winding to the level fixed by the highest system voltage completes the design verification.
The permissible loading in service is assessed with the loading guide IEC 60076-7. This matters at 1600 kVA because a planned overload on such a unit is often used instead of installing a second transformer for a temporary peak, and the guide states how long the overload may last for a given ambient temperature and preload before the winding hot-spot temperature erodes the normal insulation life.
Insulating oil conforms to IEC 60296 and is tested for power-frequency breakdown by IEC 60156 or ASTM D1816, together with moisture and acidity checks, both before energisation and at each scheduled oil sample.
Installation and Service
The unit is suitable for outdoor installation on a concrete plinth or inside a substation room with fire separation and forced or natural ventilation sized for the total loss of the transformer. Civil works must allow for the oil volume in the event of a tank rupture, and the LV cable or busbar connection must be braced for the short-circuit force corresponding to the transformer's impedance. In service the maintenance cycle combines visual inspection, bushing cleaning, tap changer operation through the full range and periodic dissolved-gas analysis of the oil.
Frequently Asked Questions
Q: What is the full-load secondary current of a 1600 kVA transformer at 400 V?
A: The LV line current is about 2310 A (1600000 / (1.732 x 400)), which is why the LV side is normally a busbar system rather than cable, and why the main breaker must have a breaking capacity above the transformer's prospective fault current.
Q: Why does short-circuit impedance matter so much at this rating?
A: The impedance determines the fault current at the LV terminals. A lower impedance gives better voltage regulation but raises the fault level that the switchgear must withstand, so IEC 60076-5 verification and the LV device ratings must be selected together.
Q: When should fans be specified in addition to a plain tank?
A: When the site ambient exceeds the reference maximum of 40 degrees C in IEC 60076-1, when the load profile produces a sustained peak, or when a future capacity increase is expected. Forced cooling raises the permissible continuous load but adds a fan supply and a control circuit that must be maintained.
Q: What does Dyn11 contribute to supply quality?
A: The delta HV winding provides a closed path for triplen harmonic currents so they do not propagate into the supply network, and it limits the voltage distortion produced by non-linear loads on the LV side.
Q: How is the sound level of a unit this size verified?
A: Sound power and sound pressure levels are determined by the methods of IEC 60076-10, and the guaranteed level forms part of the technical specification, which matters where the transformer is installed close to occupied buildings.
Q: What oil tests are performed before energisation?
A: Breakdown voltage by IEC 60156 or ASTM D1816, together with moisture content and acidity, on a sample drawn from the tank after filling and settling. The oil is supplied against the IEC 60296 specification.