23Q110 CRGO Silicon Steel Lamination Assembled Transformer Iron Core
Oct 21, 2025
Leave a message
What Is an Assembled CRGO Transformer Iron Core?
An assembled CRGO transformer iron core is a closed magnetic circuit built from laminations of cold-rolled grain-oriented electrical silicon steel. The laminations are cut from sheet, coated with an insulating layer, stacked in an interleaved step-lap pattern and clamped into two matched halves. Because the steel is grain-oriented, its magnetic properties are excellent in the rolling direction, which is aligned with the flux path of the core to minimize no-load loss and exciting current.
Assembled cores are delivered as complete, ready-to-wind structures. The coil can be wound separately around the core limb and the two halves closed afterwards, which shortens production time and improves the consistency of large distribution and power transformers.
The 23Q110 Grade and Material Properties
23Q110 is a cold-rolled grain-oriented silicon steel grade with a nominal thickness of 0.23 mm. Grain-oriented grades contain roughly 2.9% to 3.5% silicon, which raises electrical resistivity and reduces eddy current losses while keeping the magnetic anisotropy that gives high permeability in the rolling direction. The designation 23Q110 corresponds to a maximum guaranteed core loss of 1.10 W/kg measured at 1.7 T and 50 Hz by the Epstein method.
Key material properties include a high lamination factor, typically 97.2% or better for 0.23 mm material, and a minimum magnetic polarization B800 of 1.82 T, which indicates a strong cube-on-edge texture and a high usable working flux density.
Lamination and Stacking Technology
Insulated laminations: each sheet carries an inorganic insulation coating that blocks eddy currents between layers, keeping stray loss low.
Step-lap joints: adjacent layers are offset so that the joints are distributed over several steps, reducing the local flux concentration and lowering no-load loss and noise.
Precision stacking: automatic stacking machines hold the joint gap below 1.0 mm and the window height and width accuracy to +/-1 mm.
Large capacity: automatically stacked cores up to 60 tons and manually stacked cores up to 120 tons can be produced for high-power transformers.
The combination of tight joint gaps and controlled stacking pressure keeps the lamination factor high and prevents vibration at the joints during operation.
Available Grades and Typical Performance
The table lists common assembled core grades with their guaranteed maximum core loss at 1.7 T and 50 Hz, lamination factor and minimum induction at 800 A/m.
| Type | Grade | Width | Max core loss P1.7/50 W/kg | Lamination factor % | Min induction B800 T |
|---|---|---|---|---|---|
| Common | 23Q110 | 35-1200 mm | 1.10 | 97.2 | 1.82 |
| Common | 23Q120 | 35-1200 mm | 1.20 | 97.2 | 1.82 |
| Common | 27Q120 | 35-1200 mm | 1.20 | 97.5 | 1.82 |
| Common | 30G120 | 35-1200 mm | 1.20 | 98.0 | 1.82 |
| High induction | B23P085 | 35-1200 mm | 0.85 | 97.2 | 1.88 |
| High induction | B23P090 | 35-1200 mm | 0.90 | 97.2 | 1.88 |
| High induction | B27P095 | 35-1200 mm | 0.95 | 97.5 | 1.89 |
| Domain refined | B20R070 | 35-1200 mm | 0.70 | 97.0 | 1.86 |
| Domain refined | B23R085 | 35-1200 mm | 0.85 | 97.2 | 1.88 |
| Domain refined | B27RK085 | 35-1200 mm | 0.85 | 97.5 | 1.89 |
Domain-refined grades use laser scribing or similar treatment to subdivide magnetic domains, cutting anomalous eddy current loss further. They are preferred for transformers where no-load loss is the dominant operating cost.
Applications of Assembled CRGO Cores
Distribution and power transformers for transmission and distribution networks
Stator and rotor lamination stacks in electric motors, from household appliances to EV traction motors
Generator cores where low loss directly raises power output
Converter and inverter magnetic components in power electronics
Wind turbine generators, where core loss reduction improves energy yield
Design and Ordering Notes
Provide the core drawing with window dimensions, limb widths and stack height; the joint gap and stacking pressure are then set to keep loss within the grade guarantee.
Select the grade by evaluating the total owning cost: a lower-loss grade such as B23R085 pays back through reduced no-load loss over the transformer lifetime.
State the lamination factor requirement in the specification, since it directly determines the effective cross-section and therefore the working flux density.
Specify the insulation coating type when the core will be used at high temperature or in corrosive environments.
FAQ
What does 23Q110 mean?
23 refers to the nominal strip thickness of 0.23 mm, Q indicates grain-oriented material, and 110 is the maximum guaranteed core loss of 1.10 W/kg at 1.7 T and 50 Hz.
Why are transformer cores laminated?
Lamination divides the core into thin insulated sheets, which interrupts the paths of eddy currents induced by the alternating flux. This reduces eddy current loss dramatically compared with a solid iron core.
What is a step-lap joint and why is it used?
In a step-lap joint the laminations are interleaved in small offset steps instead of meeting at one straight line. This spreads the flux transition over several steps, lowering no-load loss and reducing audible noise at the joints.
What core loss can be expected from 23Q110?
The guaranteed maximum is 1.10 W/kg at 1.7 T and 50 Hz measured with the Epstein method. Actual loss depends on the joint design, stacking pressure and the working flux density chosen by the designer.
What is the maximum core size available?
Automatically stacked cores can reach 60 tons and manually stacked cores up to 120 tons, which covers the range of medium and large power transformers.
Which grade should be used for an energy-efficient distribution transformer?
For 50 Hz distribution transformers, high-induction or domain-refined grades such as B23P085 or B23R085 reduce no-load loss by 15% to 25% compared with common grades, at a higher material cost that is usually recovered through lower operating losses.