100 kVA 10 kV Copper-Winding Wound-Core Oil-Immersed Transformer

Oct 30, 2025

Leave a message

Why Use a Wound Core

A wound core is produced by winding a continuous strip of grain-oriented electrical steel into a rectangular loop and then annealing it, so the magnetic path has no bolted joint and the grain orientation follows the flux path around the corners. The practical benefits are a lower no-load loss, a lower exciting current and reduced noise compared with a stacked core assembled from a large number of bolted laminations. The cost is in winding: coils must be rectangular to fit the core window, and winding equipment has to be set up accordingly.

For a 100 kVA unit, the core is typically built from thin grain-oriented strip with a build factor around 0.96 or above, and the design flux density is usually kept between 1.6 T and 1.7 T so the core operates below the knee of the magnetisation curve.

Copper Windings and Their Effect on Loss

Copper conductors have lower resistivity than aluminium, so for the same current density a copper winding has lower load loss and less heating, which in turn allows a smaller cooling surface for the same temperature rise. Copper also has higher mechanical strength, which improves the winding's ability to withstand the forces generated by a short-circuit event.

Windings are normally layer or multi-layer types with paper or enamel insulation; the insulation system must be compatible with the insulating liquid and with the temperature class of the transformer. Interlayer insulation is designed with due allowance for impulse voltage distribution, particularly at the line end of the high-voltage winding.

Typical Ratings and Parameters

Parameter Typical Value
Rated capacity 100 kVA
High-voltage winding 10 kV class, highest voltage for equipment 12 kV
Low-voltage winding 400 V, three-phase, four-wire
Vector group Dyn11 for three-phase units, per IEC 60076-1 conventions
Tapping range Plus and minus 5 %, or two taps of 2.5 %, off-circuit
Cooling ONAN, liquid-immersed
Short-circuit impedance Typically around 4 % of rated voltage, tolerance per IEC 60076-1
Insulating liquid Mineral insulating oil to IEC 60296

Insulation Level, Losses and Temperature Rise

For a winding with a highest voltage for equipment of 12 kV, IEC 60076-3 specifies a rated lightning impulse withstand voltage of 75 kV peak and a separate-source power-frequency withstand voltage of 28 kV rms. These values, together with the induced-voltage test on the low-voltage winding, form the dielectric test basis of the unit.

Losses are declared for the reference temperature and stated on the nameplate. IEC 60076-1 permits total losses to exceed the declared value by up to 15 % and applies a tolerance of plus or minus 10 % to the declared short-circuit impedance. Temperature-rise limits are taken from IEC 60076-2: a top-liquid rise of 60 K and an average winding rise of 65 K for the standard classes. The GB/T 1094 series mirrors this structure for the Chinese market, and GB/T 6451 gives the technical parameters and loss levels for three-phase oil-immersed distribution transformers.

Tap Changing, Protection and Testing

Off-circuit tap changers are normally used at this rating. Tap-changer performance requirements and test methods are covered by IEC 60214-1. Taps are set with the transformer isolated and are locked after commissioning so that the position cannot drift.

Routine tests are those of IEC 60076-1 and include winding resistance, ratio and vector group verification, no-load loss and current, load loss and impedance, applied potential and induced potential tests. Where the purchaser specifies them, additional tests cover temperature rise, lightning impulse withstand, sound level determination to IEC 60076-10 and short-circuit withstand capability to IEC 60076-5. Oil quality is verified by dielectric breakdown testing of the insulating liquid to IEC 60156, with samples taken after filling and after the settling period.

Loading limits over the service life, including the effect of cyclic loading on insulation ageing, should be assessed using the guidance of IEC 60076-7.

Frequently Asked Questions

Q: What is the main advantage of a wound core over a stacked core?
A: The continuous magnetic path with no bolted joints lowers no-load loss, no-load current and noise, at the cost of a more complex winding process.

Q: Why specify copper instead of aluminium windings?
A: Copper gives lower load loss and better mechanical strength for the same current density, allowing a smaller cooling surface or a lower temperature rise.

Q: What insulation level applies to a 10 kV winding?
A: For a highest voltage for equipment of 12 kV, IEC 60076-3 specifies a 75 kV peak lightning impulse withstand and a 28 kV rms power-frequency withstand.

Q: What short-circuit impedance is normal at 100 kVA?
A: Around 4 % of rated voltage is typical for this rating, declared on the nameplate and subject to the tolerance of IEC 60076-1.

Q: How are losses verified?
A: No-load loss and load loss are measured as routine tests against IEC 60076-1, and total losses may not exceed the declared value by more than 15 %.

Q: Can the transformer be loaded above nameplate rating?
A: Short-term overload is possible within the limits of the loading guide in IEC 60076-7, but sustained overload accelerates insulation ageing and shortens service life.