Dry Type Transformer Core

Oct 09, 2025

Leave a message

Dry type transformer cores are the magnetic circuits used in dry-type transformers, which operate without oil or other liquid coolants. Because there is no oil, dry-type transformers are inherently fire-safe and are preferred for indoor installations, commercial buildings, industrial facilities, renewable-energy plants and electric vehicle charging stations. The core must provide an efficient magnetic flux path with low no-load loss and low noise, while supporting the compact, low-maintenance construction that dry-type designs require.

What Is a Dry-Type Transformer Core?

Like any transformer core, a dry-type core is a closed magnetic circuit built from insulated electrical steel laminations, normally cold-rolled grain-oriented silicon steel, stacked and clamped into a three-phase core assembly. The laminations carry the alternating flux of the transformer, and the insulating coating between sheets keeps eddy-current loss low. Because the core is not immersed in oil, the insulation system of a dry-type transformer relies on air or resin, so the core design emphasizes low loss (to limit heating), low noise and precise geometry (to fit the resin-cast or vacuum-impregnated windings).

Why Dry-Type Transformers Use Specially Designed Cores

The core of a dry-type transformer is designed for a different set of constraints than an oil-immersed unit:

Fire safety: with no oil, the transformer removes the fire and environmental risks of liquid leaks, which is decisive for indoor and sensitive sites.

Heat removal by air: losses must be kept low because air cooling is less effective than oil cooling; low-loss grades directly reduce the temperature rise of the windings.

Low noise: dry-type transformers are often installed near occupied spaces, so core vibration and magnetostrictive noise are controlled by joint design and clamping.

Compact volume: the core and coil assembly is designed to minimize footprint, supporting installations in urban substations and building plant rooms.

Material Grades and Magnetic Performance

The table lists typical grain-oriented grades for dry-type transformer cores. Core loss is guaranteed at P17/50 (1.7 T, 50 Hz) and P17/60 (1.7 T, 60 Hz); density is 7.65 kg/dm³; induction is the minimum value at 800 A/m field strength; and the lamination factor is a minimum.

Type Grade Thickness (mm) Max Core Loss P17/50 (W/kg) Max Core Loss P17/60 (W/kg) Min Induction (T) Min Lamination Factor
Conventional C23Q110 0.23 1.10 1.45 1.82 0.945
Conventional C23Q120 0.23 1.20 1.57 1.82 0.945
Conventional C27Q120 0.27 1.20 1.58 1.82 0.950
Conventional C27Q130 0.27 1.30 1.68 1.82 0.950
Conventional C30Q120 0.30 1.20 1.58 1.82 0.955
Conventional C30Q130 0.30 1.30 1.71 1.82 0.955
High induction C23QG085 0.23 0.85 1.12 1.88 0.945
High induction C23QG090 0.23 0.90 1.19 1.88 0.945
High induction C23QG095 0.23 0.95 1.25 1.88 0.945
High induction C23QG100 0.23 1.00 1.32 1.88 0.945
High induction C27QG090 0.27 0.90 1.19 1.88 0.950
High induction C27QG095 0.27 0.95 1.25 1.88 0.950
High induction C27QG100 0.27 1.00 1.32 1.88 0.950
High induction C27QG110 0.27 1.10 1.45 1.88 0.950
High induction C30QG105 0.30 1.05 1.38 1.88 0.955
High induction C30QG110 0.30 1.10 1.46 1.88 0.955
High induction C30QG120 0.30 1.20 1.58 1.88 0.955
Domain refined high induction C23QH080 0.23 0.80 1.06 1.88 0.945
Domain refined high induction C23QH085 0.23 0.85 1.12 1.88 0.945
Domain refined high induction C23QH090 0.23 0.90 1.19 1.88 0.945
Domain refined high induction C23QH100 0.23 1.00 1.32 1.88 0.945
Domain refined high induction C27QH085 0.27 0.85 1.12 1.88 0.950
Domain refined high induction C27QH090 0.27 0.90 1.19 1.88 0.950
Domain refined high induction C27QH095 0.27 0.95 1.25 1.88 0.950
Domain refined high induction C27QH100 0.27 1.00 1.32 1.88 0.950
Domain refined high induction C30QH095 0.30 0.95 1.25 1.88 0.955
Domain refined high induction C30QH100 0.30 1.00 1.32 1.88 0.955
Domain refined high induction C30QH110 0.30 1.10 1.46 1.88 0.955

For a given no-load-loss target, the designer selects the thinnest grade that meets the loss budget; higher-induction grades allow a smaller core cross-section at the same loss, reducing weight and footprint.

Design and Manufacturing Characteristics

Dry-type transformer cores are manufactured with the same precision as oil-immersed transformer cores: strip is cut to length, stacked with staggered (step-lap) joints to minimize the effective air gap, and clamped under controlled pressure. The completed core assembly is characterized by low no-load loss, low no-load current, low noise, high mechanical strength, good short-circuit withstand and low partial discharge. Core products of this type are supplied for transformer voltage classes from 10 kV up to 1100 kV, with dimensions matched to the winding design and insulation clearances.

Applications

Commercial buildings and office towers where fire safety rules restrict oil-filled equipment.

Industrial facilities requiring low-maintenance, indoor power distribution.

Renewable energy systems, including solar and wind plant auxiliary supplies.

Electric vehicle charging stations, where dry-type units avoid fire risk near people and vehicles.

Residential and urban substations with space constraints.

Frequently Asked Questions

Q: What is the difference between a dry type core and an oil immersed core?
Both are laminated grain-oriented silicon steel magnetic circuits. The difference is the surrounding system: a dry-type transformer cools with air or resin and has no oil, while an oil-immersed transformer uses oil for insulation and cooling. The core itself is designed to the same magnetic principles, but dry-type designs emphasize lower loss because air cooling is less effective.

Q: Why is a dry-type transformer used indoors?
Because it contains no oil, a dry-type transformer cannot leak, spray or ignite oil, so it meets fire and environmental requirements for indoor and sensitive locations where oil-filled units are restricted.

Q: What does P17/50 mean in the core loss table?
P17/50 is the specific core loss measured at a peak induction of 1.7 T with a sinusoidal flux at 50 Hz. P17/60 is the same measurement at 60 Hz; loss at 60 Hz is higher because eddy-current loss rises with frequency.

Q: How do I choose between conventional and high-induction grades?
Use the guaranteed no-load loss of the transformer as the target. High-induction grades (QG) and domain-refined grades (QH) achieve lower loss at the same thickness, allowing a smaller core for the same loss budget; the choice balances material cost against core size and weight.

Q: What is the lamination factor and why does it matter?
The lamination factor is the ratio of effective magnetic cross-section to geometric cross-section. A higher factor (0.945–0.955 for these grades) means less wasted space in the core window and a smaller core for the same flux-carrying capacity.

Q: Can dry type transformer cores be used in outdoor installations?
Yes, when housed in an appropriate weatherproof enclosure. Dry-type transformers are increasingly installed outdoors in compact enclosures where fire safety or environmental rules limit oil-filled equipment.