800 kVA 20 kV/0.4 kV Oil-Immersed Distribution Transformer for PV Plants
Nov 04, 2025
Leave a message
Solar and energy-storage projects increasingly connect to the medium-voltage network at 20 kV, and the distribution transformer at the point of interconnection has to work outdoors, in a sealed tank, at a duty cycle driven by the sun. An 800 kVA, 20/0.4 kV three-phase oil-immersed transformer in the S13-M family is a typical choice for that duty: a fully sealed corrugated tank without conservator, a low-loss core, a Dyn11 connection group matched to inverter step-up, and an insulation level that satisfies the 20 kV class test requirements.
Fully Sealed Design for Outdoor PV Duty
The transformer adopts a fully oil-filled, hermetically sealed tank. The corrugated wall is a permanently closed surface whose elasticity accommodates the change in oil volume as the load and ambient temperature vary, so no conservator and no oil storage tank are required. The cover is bolted and welded to the tank rim, isolating the oil from air and preventing both oxidation and moisture ingress.
Near-zero routine maintenance – no oil treatment, no oil-level checks and no desiccant breather to service.
Long insulation life – sealed oil ages far more slowly than oil that breathes ambient air.
Compact footprint – the corrugated wall doubles as the cooling surface and as the expansion element, so the unit is lower and smaller than a conservator-type transformer of the same rating.
Outdoor durability – the sealed construction tolerates dust, humidity and the wide temperature swings of desert, coastal and mountain PV sites.
Why the 20 kV Insulation Level Matters
Voltage class compliance is verified by two tests on the insulation structure. For the 20 kV class the power-frequency withstand test is performed at 55 kV, and the full-wave lightning impulse withstand is 125 kV at the peak, with a chopped-wave level of 140 kV where that test is specified. The 0.4 kV low-voltage winding is tested at 5 kV power frequency. These levels determine the internal clearances, the bushing selection and the insulation thickness between windings, which is why the specified voltage class must never be treated as a nominal label. For PV applications the medium-voltage side is usually a cable connection to the inverter step-up transformer or to the collector network, and the low-voltage side feeds the station auxiliary supply or the grid-tie point.
Reference Parameters for the 800 kVA Rating
The table gives reference values for the S13-M series at 20 kV class, three-phase, 50 Hz. Declared losses depend on the efficiency grade required by the project and must be confirmed for the ordered rating.
| Rated power (kVA) | HV (kV) | Tap range | LV (kV) | Connection | No-load loss (W) | Load loss (W, 75 °C) | Impedance (%) | No-load current (%) |
|---|---|---|---|---|---|---|---|---|
| 100 | 20 | ±5% or ±2×2.5% | 0.4 | Dyn11 / Yyn0 | 150 | 1730 / 1650 | 5.5 | 1.5 |
| 200 | 20 | ±5% or ±2×2.5% | 0.4 | Dyn11 / Yyn0 | 340 | 3000 / 2860 | 5.5 | 1.2 |
| 400 | 20 | ±5% or ±2×2.5% | 0.4 | Dyn11 / Yyn0 | 570 | 4970 / 4730 | 5.5 | 0.9 |
| 630 | 20 | ±5% or ±2×2.5% | 0.4 | Dyn11 / Yyn0 | 810 | 6200 | 6.0 | 0.8 |
| 800 | 20 | ±5% or ±2×2.5% | 0.4 | Dyn11 / Yyn0 | 700 | 8250 | 6.0 | 0.7 |
| 1000 | 20 | ±5% or ±2×2.5% | 0.4 | Dyn11 / Yyn0 | 830 | 10300 | 6.0 | 0.6 |
Two points should be read with care. Load loss is declared at a stated reference temperature, here 75 °C, and figures from documents using a different reference temperature are not directly comparable. Adjacent capacity steps may also be declared under different efficiency classes, so the declared loss of a larger rating is not automatically higher than that of a smaller one; the guaranteed value for the ordered rating and its efficiency class governs.
The insulation levels that apply to the voltage classes relevant to this transformer type are listed below.
| Voltage class (kV) | Max operating voltage (kV) | Power-frequency withstand (kV, 1 min) | Lightning impulse (kV peak) |
|---|---|---|---|
| 0.4 | 0.46 | 5 | Not applicable |
| 10 | 12 | 35 | 75 full / 85 chopped |
| 20 | 23 | 55 | 125 full / 140 chopped |
Applications and System Benefits
Solar and storage grid-tie – Dyn11 with a 20/0.4 kV ratio matches inverter step-up and interconnection requirements, while the low-loss core cuts the continuous energy cost of a plant that operates for decades.
Safety-critical buildings – hospitals, schools and shopping centres benefit from the fully enclosed construction, which removes oil-leakage risk in basements and plant rooms.
Commercial and industrial sites – sealing against moisture and dust, together with the omission of the conservator, reduces maintenance work and installation space.
Integrated prefabricated substations – the same transformer design is used in PV compact substations and in energy-storage container substations, where the transformer, switchgear, protection, busbars and monitoring are factory assembled and tested as one unit before shipment, cutting site works and commissioning time.
Selection Points for a PV Project
Confirm rated capacity from the calculated maximum demand of the inverter block, with allowance for future expansion.
State the voltage ratio, vector group and tap range together, because they fix the winding design and the protection settings.
State the site altitude and the maximum and minimum ambient temperature; both affect clearances and permissible temperature rise.
Specify the transformer oil grade for the lowest expected ambient temperature.
For ratings of 630 kVA and above, specify the required accessories, typically a gas relay and a temperature controller.
Confirm the local efficiency grade and the loss values that must be guaranteed on the test certificate.
Allow ventilation clearance around the corrugated tank and provide a level, non-settling foundation.
Frequently Asked Questions
Q: Why is a fully sealed tank preferred in a PV plant?
The sealed corrugated tank removes the oil-to-air interface, so oil oxidation and moisture ingress are largely eliminated and routine maintenance is limited to external inspection.
Q: Which insulation tests apply at 20 kV?
A power-frequency withstand test at 55 kV for one minute and a full-wave lightning impulse withstand of 125 kV peak, with a chopped-wave level of 140 kV where that test is specified.
Q: Which connection group is used for inverter step-up?
Dyn11 is the usual selection because it matches inverter step-up and grid-interconnection practice; Yyn0 is available where the low-voltage network requires it.
Q: What are the reference losses for 800 kVA?
About 700 W no-load loss and about 8250 W load loss at the stated 75 °C reference, with 6.0% impedance and 0.7% no-load current, subject to confirmation against the required efficiency grade.
Q: Why can load-loss figures differ between documents?
Load loss depends on the reference temperature at which it is declared. Values quoted at different reference temperatures must be corrected to one common temperature before they are compared.
Q: What information is needed before the transformer is ordered?
Rated capacity, voltage ratio, vector group, tap range, altitude, ambient temperature, indoor or outdoor installation, oil grade, required accessories and the applicable efficiency grade.