160 kVA Three-Phase Oil-Immersed Distribution Transformer

Oct 31, 2025

Leave a message

Energy-Efficient Design

The 160 kVA three-phase oil-immersed distribution transformer is built around a premium silicon steel core that significantly reduces operational losses, minimizes energy waste, and operates with low noise. The windings use heat-resistant enameled wire, which maintains excellent conductivity and stability even under high load conditions, reducing line losses and extending the transformer's lifespan. The combination of a low-loss core and high-quality windings gives the unit high efficiency across its load range.

Flexible Customization

Diverse voltage configurations are available, with high-voltage options including 6 kV, 6.3 kV, 10 kV, 10.5 kV, 11 kV, 20 kV, and 35 kV, and low-voltage options of 0.4 kV, 400 V, or 415 V. Multiple connection groups such as Dyn11 and Yyn0 are supported, allowing the transformer to match different local grid requirements and earthing practices.

Technical Parameters

Parameter Value (160 kVA)
High voltage 11 kV / 10.5 kV / 10 kV / 6.3 kV / 6 kV
Tap range plus or minus 5 percent or plus or minus 2 x 2.5 percent
Low voltage 0.4 kV / 0.69 kV
Connection group Dyn11 or Yyn0
No-load loss 280 W
Load loss 2310 / 2200 W
No-load current 1.6 percent
Short-circuit impedance 4 percent

Product Characteristics

Winding structure: the high-voltage winding uses a multi-layer cylindrical, continuous, or connecting-continuous structure, improving impulse distribution, minimizing magnetic leakage, and providing high mechanical strength and short-circuit resistance. Core design: cold-rolled grain-oriented silicon steel sheets with full diagonal seam stacking substantially reduce no-load loss and no-load current. Fastening: cores and windings are fixed with self-locking anti-loosening nuts, and the non-hanging center structure absorbs vibration during transport and operation. Vacuum processing: vacuum drying of coils and cores and vacuum-filtered oil injection minimize internal moisture. Oil tank: the corrugated sheet tank has a breathing function that compensates oil volume changes with temperature, eliminating the oil conservator and reducing overall height.

Applications

These transformers are used in power plants, substations, industrial and mining enterprises, and rural power grids, providing efficient power distribution for workshops, commercial buildings, agricultural facilities, and small communities.

Frequently Asked Questions

Q: What load can a 160 kVA transformer supply?

A: At 0.4 kV with a typical power factor of 0.85, the unit can supply roughly 130 kW of continuous load, suitable for a small factory, a commercial building, or a rural community cluster.

Q: What is the difference between Dyn11 and Yyn0?

A: Dyn11 has a delta-connected high-voltage winding with a star-connected low-voltage winding and a 30-degree phase shift; Yyn0 has both sides star-connected with no phase shift. Dyn11 handles unbalanced loads better.

Q: How are no-load and load losses defined?

A> No-load loss is the power consumed by the core when the transformer is energized with no load; load loss is the power lost in the windings at rated current. Both values are measured at reference temperature per IEC 60076.

Q: Why is the corrugated tank maintenance-free?

A: The corrugated sheets flex to absorb oil expansion, and the sealed design prevents air and moisture ingress, so the oil does not oxidize and no conservator or routine oil change is needed.

Q: Can the transformer operate at 60 Hz?

A: Yes. 50 Hz and 60 Hz versions are both available, with core flux density and cooling design adjusted accordingly.

Q: What tests are performed before delivery?

A: Routine tests include winding resistance, ratio, polarity, no-load loss and current, load loss and impedance, and dielectric tests; type tests such as lightning impulse and temperature rise are available on request.