160 kVA Oil Immersed Transformer: Technical Guide for 10 kV Distribution Projects

Oct 31, 2025

Leave a message

Product Overview: 160 kVA Oil Immersed Transformer

A 160 kVA oil immersed transformer is a three-phase distribution unit in which the core-and-coil assembly is immersed in insulating mineral oil inside a sealed or conservator-type tank. The oil performs two functions at once: electrical insulation between windings and heat transfer to the tank wall.

This construction remains the industry standard for 10 kV class distribution networks and is a first choice for utilities, factories, construction sites and agricultural feeders where reliability under continuous load matters more than the smallest possible footprint. The low-loss S11-type design reduces no-load loss through an optimised laminated core and a carefully controlled magnetic circuit; against older S9 designs, S11-class units typically cut no-load loss by roughly 15-20 %, which directly lowers the annual cost of feeding a lightly loaded distribution line.

Most 160 kVA units are applied at 10 kV or 11 kV primary with a 0.4 kV secondary. A 35 kV primary is available only as an engineered special at this capacity, because the insulation and bushing arrangement then differs from the standard 10 kV platform.

Reference Specification Table

Parameter Standard configuration Note
Rated capacity 160 kVA Continuous rating per IEC 60076-1
Primary voltage 10 kV or 11 kV, 6.3 kV optional 35 kV only as engineered special
Secondary voltage 0.4 kV, 400/230 V Other low-voltage taps by project
Vector group Dyn11 default, Yyn0 available Dyn11 recommended for unbalanced load
Impedance voltage 4.0-4.5 % Sized with the project short-circuit study
No-load loss Up to 0.40 kW, S11-class target Checked against GB/T 6451 limits
Load loss at 75 °C Up to 2.9 kW Copper or aluminium windings
Frequency 50 Hz or 60 Hz Tap range and impulse level set by the grid
Cooling ONAN Oil natural, air natural
Insulation and oil Class A 105 °C, inhibited mineral oil Vacuum filled before sealing
Typical tank size About 1210 × 780 × 1280 mm Outline varies between makers

All figures are reference values for the standard configuration. The binding values are the ones in the factory type-test certificate issued per IEC 60076-1, and loss figures should be compared with the limits of the GB/T 6451 series before the order is placed.

Design Features That Matter in Service

Short-circuit withstand

The winding is braced with a low-axial-force structure so that the axial forces generated during a through-fault are contained without coil deformation. High-tensile clamping keeps the coil stack under controlled compression, and the complete unit is verified against the short-circuit test requirements of IEC 60076-5; low-voltage foil or helical windings are used where the short-circuit duty is high.

Corrosion and sealing

All cover bolts and fasteners are 304 stainless steel to resist rust in humid or coastal environments. Sealing gaskets are chosen for long-term oil retention, and the tank receives a corrosion-resistant paint system. For flood-prone sites a fully sealed tank without conservator is available, in which the corrugated or fin wall absorbs the oil volume change.

Core and loss performance

The laminated core is built from cold-rolled grain-oriented silicon steel with a step-lap joint to keep magnetising current low. Operating flux density is set conservatively so that the core does not saturate at 105 % of rated voltage, which also keeps the third-harmonic content of the no-load current small. No-load loss dominates total loss on a lightly loaded distribution feeder, so the certified no-load figure is the most important single number in the type test.

Temperature rise and loading

Winding temperature rise and top-oil temperature rise follow IEC 60076-2 limits for liquid-immersed transformers. Continuous loading at the nameplate rating is permitted at ambient temperatures up to 40 °C, with derating above 1,000 m altitude per IEC 60076-1 and additional attention to cooling where the transformer is installed in a closed enclosure.

Typical Applications

Rural and urban 10 kV distribution feeders serving mixed residential and light industrial load.

Factory incoming substations where a compact, low-maintenance power source is required.

Construction sites and temporary power supply, where the Dyn11 connection tolerates single-phase load imbalance from tools and welding circuits.

Agricultural pumping stations and small commercial complexes operating at 400/230 V utilisation voltage.

Public facilities such as clinics, schools and water treatment plants that need a quiet, sealed unit close to the load.

Selection and Procurement Checklist

Fix the primary voltage, vector group and impedance voltage with the network operator before ordering.

Request the type-test report per IEC 60076-1 covering no-load loss, load loss and temperature rise, and check the losses against the GB/T 6451 loss limits.

Specify terminal arrangement, oil type and the choice between conservator and fully sealed tank.

Confirm the accessory set: pressure relief device, oil-level gauge, thermometer pocket and drain valve, plus a gas relay where a conservator is used.

State the site altitude, ambient temperature range and any corrosive or dusty atmosphere so that derating and coating can be settled at the design stage.

Check the outline drawing and tank mass against the transport route, crane capacity and pad dimensions.

FAQ

Q: Can a 160 kVA unit be supplied with a 35 kV primary?
A 160 kVA rating is distribution class and is normally designed for 10-11 kV. A 35 kV primary at this capacity is possible only as a non-standard engineered design, and the voltage, impulse level and impedance must be agreed at the design stage rather than taken from a catalogue table.

Q: What no-load loss should be expected?
For an S11-class 160 kVA unit the no-load loss is typically in the 0.28-0.40 kW range. The exact value follows the GB/T 6451 series and the manufacturer type-test certificate.

Q: Which vector group suits an unbalanced load?
Dyn11 is the default. The delta winding provides a path for zero-sequence and third-harmonic currents, which keeps the secondary voltage balanced when single-phase tools, lighting or small motors are unevenly distributed. Yyn0 is available for networks that require it.

Q: How is the transformer protected against overpressure?
A pressure relief device opens when internal pressure becomes abnormal and reseats once pressure returns to normal. An oil-level gauge and a thermometer pocket allow oil level and top-oil temperature to be monitored without opening the tank.

Q: What is the typical production time?
Standard 160 kVA units are usually produced within 25-40 days after order confirmation, subject to the accessory list and test scheduling. Non-standard primary voltages and special enclosures extend the schedule.

Q: What determines the impedance voltage?
The project short-circuit study. The 4.0-4.5 % band covers most 160 kVA distribution applications, but a higher value reduces fault current on the low-voltage side and a lower value improves voltage regulation; the choice must be coordinated with the switchgear rating.