100 kVA Oil Immersed Transformer for Construction Sites and Temporary Power Supply
Jan 22, 2026
Leave a message
Key Takeaways
- A 100 kVA oil-immersed transformer is a compact, self-contained power hub for cranes, welders, site cabins and lighting towers.
- Standard primary ratings are 11 kV (95 kV BIL) or 13.8 kV (110 kV BIL); 33 kV is not available at this capacity.
- Choose Dyn11 connection so single-phase loads (welding, tools) do not unbalance the feeder.
- Specify skid base or trailer mount, IP54+ enclosure and pressure-relief device for site duty; every unit ships with an IEC 60076 routine test report.
1. Why a 100 kVA Oil-Immersed Transformer for Site Power?
Construction sites and temporary installations need a power source that is electrically sound, physically rugged and quick to redeploy. A 100 kVA oil-immersed distribution transformer fits this duty because the oil-immersed construction provides inherent thermal mass: short-term peak loads from cranes, hoists and welders are absorbed without exceeding the winding temperature limits defined in IEC 60076-2. The sealed tank and insulating oil also protect the windings from dust, moisture and temperature swings that are unavoidable on an active site.
Because the unit is a factory-built, pre-tested package, commissioning is reduced to cable connection, earthing and energization. That is the difference between a site transformer and a fixed substation: the transformer is a service tool, not a project in itself.
Technical Specification
| Parameter | Specification |
|---|---|
| Rated capacity | 100 kVA, continuous rating per IEC 60076-1 |
| Primary voltage / BIL | 11 kV / 95 kV BIL (standard), 13.8 kV / 110 kV BIL (optional) |
| Secondary voltage | 400/230 V or 480/277 V |
| Vector group | Dyn11 (recommended for unbalanced site loads) |
| Impedance voltage | 4.0–4.5% |
| Cooling | ONAN |
| Enclosure protection | IP54 (standard), higher on request (IEC 60529) |
| Ambient temperature | -25 °C to +40 °C |
| Noise level | < 55 dB(A) at 1 m (typical, per IEC 60076-10) |
| Mounting | Skid base, lifting lugs, or trailer mount |
Note: a 33 kV primary is not offered at 100 kVA; distribution transformers at 33 kV normally start at 630 kVA. Contact our engineering team if you need a higher voltage class.

A GNEE 100 kVA Oil Immersed Transformer ,positioned on gravel at an active construction site.
3. Typical Applications on Site
- Heavy machinery: tower cranes, concrete pumps, pile drivers and large excavators.
- Site cabins and workshops: lighting, HVAC, computers and small power tools.
- Welding and fabrication: multiple industrial welding stations fed from one stable LV bus.
- Lighting towers and events: large-area lighting, festivals, outdoor exhibitions and film-set power.
4. Ruggedized Design Features
- Reinforced tank: extra bracing and radiators protect against transport shock and on-site handling.
- Protected bushings: elevated or covered HV bushings reduce accidental impact damage.
- Lockable compartments: secure enclosures for metering, protection devices and LV terminations.
- Flood option: hermetically sealed (no-conservator) tank for high-flood-risk sites.
- Corrosion protection: multi-coat tank paint system tested for humid and coastal environments.

Close-up detail of the heavy-duty, corrosion-resistant paint coating on a transformer tank.
5. Mobility, Logistics and Commissioning
- Skid or trailer mounting: ready for forklift/crane lifting or towing between sites.
- Pre-wired and pre-tested: delivered oil-filled and routine-tested; connect, earth and energize.
- Export packaging: sea and land transport packaging engineered for remote project locations.
6. Site Safety and Compliance
- Pressure-relief device: automatic venting in case of internal fault.
- Earthing lugs: prominent, clearly marked connections for proper site earthing.
- Warning labels: multilingual safety instructions on tank and LV compartment.
- Compliance: design and routine testing per IEC 60076-1/-2/-3.
7. FAQ
Q: What voltage and BIL options are available for a 100 kVA oil-immersed transformer?
A: Standard options are 11 kV (95 kV BIL) and 13.8 kV (110 kV BIL) primary with 400/230 V or 480/277 V secondary. A 33 kV primary is not offered at this capacity, because the rating class normally starts at 630 kVA.
Q: Is the transformer pre-tested before delivery?
A: Yes. Every unit is routine-tested per IEC 60076-1 (ratio, losses, no-load current, dielectric, temperature rise) and delivered with the test report.
Q: Can the unit be re-located during the project?
A: Yes. Skid-mounted units are designed for repeated forklift/crane relocation, and trailer-mounted units can be towed between sites.
Don't let power reliability be a bottleneck on your construction timeline. The GNEE 100 kVA Oil Immersed Transformer is engineered as a robust, mobile, and dependable power source tailored for the toughest temporary supply challenges.
Contact GNEE today to discuss your specific site requirements and get a quote for a durable 100 kVA Oil Immersed Transformer. Let us energize your progress.