Description
Technical Parameters
Henan GNEE Electric Co., Ltd. is one of the leading manufacturers and suppliers of 630 kva oil cooled power transformer in China, also supports customized service with low price. Welcome to buy discount 630 kva oil cooled power transformer for sale here from our factory. If you have any enquiry about pricelist, please feel free to email us.
Product Description
The oil filled self cooled transformer has prominent advantages. Its oil - cooling system ensures efficient heat dissipation, maintaining stable operation under heavy loads. High - quality core and windings minimize energy loss, boosting efficiency. It offers strong short - circuit resistance and reliable insulation, enhancing safety. With a robust structure, it suits harsh industrial environments. Easy to maintain, it reduces operating costs. Ideal for power grids, industrial plants, etc., it ensures continuous power supply and stable voltage, meeting diverse application needs.
If you wish to obtain more detailed information, please feel free to contact us via email at sales@gneesteels.com.
product video
Technical data sheet

Installation and Maintenance of 630 kVA Oil Cooled Power Transformer
Installation Key Points
Pre-Installation Preparation
Verify the foundation before installation to ensure its centerline, elevation, and strength meet design requirements, with a flat and stable site. Inspect the oil cooled power transformer's exterior and accessories for completeness to confirm no transport damage.
Transportation and Positioning
Use designated load-bearing points for loading/unloading. Control the traction speed ≤2m/min during overland transport. When positioning, use jacks and other tools to ensure uniform force application, and secure the oil natural air natural transformer firmly after placement.
Oil Filling and Nitrogen Purging
For nitrogen-filled transportation, inject purified oil from the bottom and purge nitrogen from the top during oil filling. After filling, let the oil immersed self cooled transformer stand for ≥12 hours (for 500kV and below). Alternatively, use vacuum nitrogen purging, selecting a well-ventilated location for the purge outlet, and inject dry air when breaking the vacuum.
Core Inspection
If transportation is uneventful and meets no-inspection criteria (e.g., manufacturer certification, capacity ≤1000kVA), core inspection may be waived. Otherwise, inspect the core by lifting the cover in favorable weather, controlling exposure time (≤16h at ≤65% humidity; ≤12h at ≤75% humidity). Check the tightness and insulation of the core, windings, and leads.
Maintenance Key Points
Daily Inspection
Regularly check for oil leakage, abnormal noises, or overheating. Monitor oil level and color to ensure oil quality. Clean radiators to prevent blockages affecting heat dissipation. Tighten terminal connections and inspect the grounding system for integrity.
Electrical Testing
Perform periodic insulation resistance tests (using a megohmmeter), ground resistance tests, and contact resistance tests. Detect partial discharges to identify insulation degradation. For newly commissioned or overhauled oil cooled transformers, conduct inrush closing tests (5 times for new products, 3 times after overhauls).
Oil Management
Regularly sample and test insulating oil for physicochemical properties, gas composition, PCB/furan content, and power factor. When oil quality is abnormal, treat it with a vacuum oil filter to ensure indicators like breakdown voltage and water content meet standards.
Periodic Overhauls
Divided into major overhauls (recommended every 8–10 years of operation) and minor overhauls. Major overhauls include core lifting, cleaning/maintenance of the core and tank, tap changer and accessory maintenance, and oil replacement. Minor overhauls focus on external cleaning, oil level adjustment, silica gel replacement, and routine tests.
Through standardized installation and regular maintenance, the 630 kVA oil cooled power transformer ensures long-term stable and efficient operation, adapting to power demands in industrial, grid, and other scenarios.



Company Quality Policy
Our quality policy is: "Customer satisfaction is Gnee's pursuit." We uphold the principles of quality - first and customer - oriented. By relying on quality to thrive and excellence to win, we are committed to designing and manufacturing power transformers that meet diverse customer requirements, aiming for mutual development.
Want the full scoop? Shoot us an email at sales@gneesteels.com-we're here to help!
Hot Tags: 630 kva oil cooled power transformer, China 630 kva oil cooled power transformer manufacturers, suppliers, factory, 20kv oil immersed current transformer, 1000 kva oil filled transformer, 20kv oil immersed hermetically sealed type transformer, oil immersed transformer, 20kv Series Oil Immersed Distribution Transformer, hermetically sealed oil filled transformer