IEC 60076 Distribution Type Transformer
video

IEC 60076 Distribution Type Transformer

Gnee, with 18 years of transformer export experience, manufactures this IEC 60076 distribution type transformer with a rated capacity of 30-2500 KVA.
Send Inquiry
Chat Now

Description

Technical Parameters

Henan GNEE Electric Co., Ltd. is one of the leading manufacturers and suppliers of iec 60076 distribution type transformer in China, also supports customized service with low price. Welcome to buy discount iec 60076 distribution type transformer for sale here from our factory. If you have any enquiry about pricelist, please feel free to email us.

 

Product Introduction

IEC 60076 is an international standard series specifying requirements for power transformers, including distribution transformers. A  distribution type transformer is a common low-to-medium power device designed to step down or step up voltage in electrical distribution networks, typically connecting high-voltage transmission lines to low-voltage consumer systems (e.g., 11 kV to 400 V).

For more detailed information, please do not hesitate to contact us at sales@gneesteels.com.

Contact now

Product video

 

gnee supply

Models:
S11-M S13-M S20-M S22-M SH15-M (Amorphous Alloy Power Transformer)

Technical Specs:

Voltage Level: 6kV-220kV

Frequency: 50Hz/60Hz

Rated Capacity: 30kVA-2500kVA

No-load Loss: 33W-2340W

Load Loss: 430W-22220W

No-load Current: 2.1%-0.4%

Short Circuit Resistance: 4%-6%

ISO-certified, Customization available, 2-years warranty, 100% QC passed
Contact us to learn more or request a quote!

hermetically sealed distribution transformersealed transformer

 

Technical specification

S22-M-30~2500/10Distribution Transformer (Grade 1 Energy Efficiency) High - voltage (kV):6, 6.3, 10, 10.5 Low - voltage (kV):0.4
Tap:±5%, ±2×2.5% Connection group designation:Dyn11, Yyn0
Rated Capacity (kVA) No-load Loss (kW) Load Loss (kW) (at 75℃) No-load Current (%) Short-circuit Impedance (%)
30 65 455/430 1.5 4
50 80 655/625 1.3 4
63 90 785/745 1.2 4
80 105 945/900 1.2 4
100 120 1140/1080 1.1 4
125 135 1360/1295 1.1 4
160 160 1665/1585 1 4
200 190 1970/1870 1 4
250 230 2300/2195 0.9 4
315 270 2760/2630 0.9 4
400 330 3250/3095 0.8 4
500 385 3900/3710 0.8 4
630 460 4460 0.6 4.5
800 560 5400 0.6 4.5
1000 665 7415 0.6 4.5
1250 780 8640 0.5 4.5
1600 940 10440 0.5 4.5
2000 1085 13180 0.4 5
2500 1280 13360 0.4 5

 

Testing of IEC 60076 Distribution Type Transformers

Testing ensures compliance with IEC 60076 standards for safety, reliability, and performance. Below are key tests for distribution transformers (e.g., 100 kVA units):

1. Routine Tests (Conducted on Every Transformer)

These verify basic functionality and insulation integrity.

Winding Resistance Test

Measures DC resistance of primary/secondary windings to check for loose connections or defects.

Purpose: Ensure uniformity and detect soldering/welding issues.

Voltage Ratio and Phase Displacement Test

Compares the voltage ratio between primary and secondary windings against design specs.

Checks phase relationship (critical for three-phase transformers).

Tool: Digital voltage ratio tester.

Insulation Resistance Test (IR Test)

Applies high DC voltage (e.g., 500V or 1000V) to measure insulation resistance between windings and ground.

Purpose: Identify moisture, contamination, or degradation in insulation (paper, oil, or solid insulation).

Hipot (High-Potential) Test

Applies a high AC/DC voltage (e.g., 2.5x rated voltage) for a short time to test dielectric strength.

Purpose: Ensure insulation can withstand overvoltages without breakdown.

2. Type Tests (Conducted on a Sample Unit)

These validate design compliance and performance under extreme conditions.

Temperature Rise Test

Runs the power distribution transformer at full load until thermal equilibrium is reached.

Measures temperature of windings (via resistance), oil, and core.

Standards: Must stay below IEC-specified limits (e.g., 65K rise for oil-immersed windings).

Impulse Voltage Test (Lightning Surge Test)

Applies high-voltage impulse waves (1.2/50 µs waveform) to simulate lightning or switching surges.

Monitors voltage distribution and insulation response using an oscilloscope.

Purpose: Verify protection against transient overvoltages.

Noise Level Measurement

Measures acoustic noise (in dB) at specified distances (e.g., 1m from the power distribution transformer).

Requirement: Critical for urban installations to meet environmental noise regulations.

Load Loss and Impedance Voltage Test

Measures power loss (I²R losses) in windings at full load and impedance voltage (voltage drop under load).

Calculates: Short-circuit impedance percentage (e.g., 4–6% for IEC 60076 distribution type transformers).

3. Special Tests (Optional, Based on Customer/Application Needs)

Short-Circuit Withstand Test

Subjects the distribution type transformer to sustained short-circuit currents to check mechanical and thermal stability.

Purpose: Ensures it can survive faults without winding deformation or insulation failure.

Partial Discharge (PD) Test

Detects small electrical discharges in insulation (e.g., voids in oil or solid insulation).

Tool: PD detector; limits are specified in IEC 60076-3.

Dielectric Frequency Withstand Test

Applies increased frequency (e.g., 100–200 Hz) at rated voltage to test insulation under prolonged stress.

Use Case: For distribution type transformers used in variable frequency drives (VFDs) or renewable energy systems.

Oil Tests (For Oil-Immersed Transformers)

Breakdown Voltage Test: Measures the oil's dielectric strength (should be ≥30 kV for new oil).

Dissolved Gas Analysis (DGA): Detects gases (e.g., H₂, CH₄) to identify early faults (thermal or electrical).

4. Three-Phase Transformer Specific Tests

Phase Sequence Test

Verifies the order of phase voltages (A-B-C or A-C-B) for three-phase windings.

Zero Sequence Impedance Test

Measures impedance under unbalanced loads (critical for grounding and fault protection).

Test Standards and Documentation

IEC 60076-1: General requirements for testing.

IEC 60076-2: Temperature rise tests.

IEC 60076-3: Insulation levels and dielectric tests.

IEC 60076-5: Short-circuit testing procedures.

 

Fields of application

hermetic transformer

 

Facory display

IEC 60076 Distribution Type Transformer factory

 

FAQ

Q: What is ester oil in transformers?
A: Ester oil in transformers is a biodegradable insulating and cooling fluid, offering higher fire resistance and environmental safety than traditional mineral oil.

Q: What is an oil-filled transformer?
A: An oil-filled transformer is an electrical device that uses insulating oil (like mineral or ester oil) as both a coolant and dielectric medium. The oil helps dissipate heat generated during operation and prevents electrical arcing between components, ensuring safe and efficient power transfer between voltage levels. It is widely used in power grids, industries, and commercial settings for its reliability and thermal performance.

Q: What kind of oil is used in transformers?
A: Transformer oils mainly include three types:
Mineral Oil: Derived from petroleum, it offers good insulation and heat dissipation but is flammable and non-biodegradable.
Synthetic Oil (e.g., Silicone Oil): Chemically produced, it is heat-resistant, non-flammable, and used in high-temperature or fire-sensitive environments.
Ester Oil (Natural/Synthetic): Extracted from plants or chemically synthesized, it has low flammability, biodegradability, and is eco-friendly, suitable for indoor use or ecologically sensitive areas.

For more information on oil-Immersed transformers, please contact us at sales@gneesteels.com.

Contact now

 

 

Hot Tags: iec 60076 distribution type transformer, China iec 60076 distribution type transformer manufacturers, suppliers, factory, 1000 kva oil filled transformer, 20kv hermetically sealed oil filled transformer, 20kv oil immersed current transformer, 20kv oil immersed hermetically sealed type transformer, hermetically sealed oil filled transformer, oil immersed transformer